Most Asked MCQ On Switchgear & Protection For Electrical JE/AE Exam

1. A thermal protection switch provides protection against what? (a)
a. Overload
b. Temperature
c. Short circuit
d. Overvoltage

Ans: a

2. What is/are the main disadvantage of using oil as the quenching
medium in the circuit breakers? 
a. Need periodical replacement.
b. Risk of formation of an explosive mixture with air.
c. Possibility of causing fire hazards.
d. All of the above.

Ans: d

3. Which of the following circuit breakers is used for the railway
electrification? 
a. Air blast circuit breaker
b. SF6 circuit breaker
c. Bulk oil circuit breaker
d. Minimum oil circuit breaker

Ans: a

4. Which circuit breaker is preferred to be installed in extra high
voltage AC system? 
a. Bulk oil type circuit breaker
b. Air blast circuit breaker
c. SF6 circuit breaker
d. Vacuum circuit breaker

Ans: c

5. Which of the following materials can be used as an arc quenching
medium in high Rupturing Capacity (HRC) fuse? 
a) Aluminium
b)Argon gas
c) Mica
d) Plaster of paris

Ans: d

6. The phenomenon of current chopping mainly occurs in which type of circuit breaker? 
a) Oil circuit breaker
b)Air blast circuit breaker
c) SF6 circuit breaker
d)Vaccum circuit breaker

Ans: b

7. The arrangement given is of protection of alternator against 

switchgear

a)Turn-turn fault in any single stator winding
b)Insulation failure of the stator winding
c)Unbalancing loading
d)Earth fault 

Ans: c

8. SF6 gas 
a)Is yellow in colour
b)Is lighter than air
c)Is nontoxic
d)Has pugment smell

Ans: c

9. Arc in a circuit behave as 
a. A capacitive reactance
b. An inductive reactance
c. A resistance increasing with voltage rise across the arc
d. A resistance decreasing with voltage rise across the arc 

Ans: d

10. A three-phase circuit breaker is rated 2000 MVA, 33 kV. What will
be its making current? 
a. 35 kA
b. 49 kA
c. 70 kA
d. 89 kA

Ans: d

11. For which among the following the current ratings are not required?
a. Circuit breakers
b. Relays
c. Isolators
d. Load break switch

Ans: c

12.Protective relays can be designed to respond to ___________. 
a. Light intensity, impedance
b. Temperature, resistance, reactance
c. Voltage and current
d. All of these

Ans: d

13. On what factor does the operating speed of the relay depend? 
a. Rate of flux built up
b. Armature core air gap
c. Spring tension
d. All of these 

Ans: d

14. Plug setting of an electromagnetic relay can be altered by varying 
a. Number of ampere turns
b. Air gap of magnetic path
c. Adjustable back stop
d. None of these

Ans: a

15. Which of the following circuit breakers has the lowest operating voltage? 
a. SF6 circuit breaker
b. Air break
c. Air blast
d. Minimum oil circuit breaker

Ans: b

16. The arcing contacts in a circuit breaker are made of
(a) copper tungsten alloy
(b) porcelain
(c) electrolytic copper
(d) aluminium alloy

Ans: a

17.Air blast circuit breaker is used for
(a) over currents
(b) short duty
(c) intermittant duty
(d) repeated duty

Ans: d

18. The current zero interruption, in oil and air blast circuit breakers, is
achieved by
(a) lengthening of the gap
(b) cooling and blast effect
(c) both (a) and (b)
(d) deionizing the oil with forced air

Ans: c

19. Directional relays are based on flow of
(a) power
(b) current
(c) voltage wave
(d) all of the above

Ans: a 

20. A differential relay measures the vector difference between
(a) two currents
(b) two voltages
(c) two or more similar electrical quantities
(d) none of the above

Ans: c

21.A transmission line is protected by
(a) inrush protection
(b) distance protection
(c) time graded and current graded over current protection
(d) both (b) and (c)

Ans: d
22. Protective relays are devices that detect abnormal conditions in
electrical circuits by measuring 
(a) current during abnormal condition
(b) voltage during abnormal condition
(c) constantly the electrical quantities which differ during normal and abnormal conditions
(d) none of the above

Ans: c
23.The voltage appearing across the contacts after the opening of the circuit breaker is called______voltage.
(a) recovery
(b) surge
(c) operating
(d) arc

Ans: a

24. The arc voltage produced in A.C. circuit breaker is always
(a) in phase with the arc current
(b) lagging the arc current by 90′′
(c) leading the arc current by 90°
(d) none of the above

Ans: a

25. The time of closing the cycle, in modern circuit breakers is
(a) 0.003 sec
(b) 0.001 sec
(c) 0.01 sec
(d) 0.10 sec

Ans: a

26.H.R.C. fuses provide the best protection against
(a) overload
(b) reverse current
(c) open-circuits
(d) short-circuits

Ans: d

27. Resistance grounding is used for voltage between
(a) 33kVto66kV
(b) HkVto33kV
(c) 3.3kVandllkV
(d) none of the above

Ans: c

28. The contacts of high voltage switches used in power system are submerged in oil. The main purpose of the oil is to
(a) lubricate the contacts
(b) insulate the contacts from switch body
(c) extinguish the arc
(d) all of the above

Ans: c
29. Wave trap is used to trap waves of
(a) power frequencies
(b) higher frequencies entering generator or transformer units
(c) either of the above
(d) none of the above

Ans: b

30. Circuit breakers usually operate under 
a) Steady short circuit current
b) Sub transient state of short circuit current
c) Transient state of short circuit current
d) None of these 

Ans: c
31.The interaction between a transmission line and communication line is minimized by
(a) transposing transmission as well as communication lines
(b) increasing the height of the transmission line tower
(c) increasing the distance between the two lines
(d) all of the above

Ans: d

32. Discrimination between main and back up protection is provided by the use of relays which are
(a) fact
(b) sensitive
(c) slow
(d) none of the above

Ans: c

33. Induction cup relay is operated due to changes in
(a) current
(b) voltage
(c) impedance
(d) all of the above

Ans: d

34. Air-blast circuit breakers for 400 kV power system are designed to operate in 
(a) 100 microsecond
(b) 50 millisecond
(c) 0.5 sec
(d) 0.1 sec

Ans: b

35.The torque produced in induction type relay (shaded pole structure) is
(a) inversely proportional to the current
(b) inversely proportional to the square of the current
(c) proportional to the current
(d) proportional to square of the current

Ans: b

36. To limit short-circuit current in a power system are used.
(a) earth wires
(b) isolators
(c) H.R.C. fuses
(d) reactors

Ans: d

37. Why is the resistance switching used in an air blast circuit breaker? 
a. Reduce the magnitude of fault current.
b. Control the CB operating time.
c. Damp out the fast transient.
d. Change the fault current power factor.

Ans: c

38. A Buchholz relay is used for: 
a) Protection of a transformer against all internal faults
b) Protection of a transformer against external faults
c) Protection of a transformer against both internal and external faults
d) Protection of induction motors

Ans: a

39. Mho relay is usually employed for the protection of 
a) Short line only
b)Medium lines only
c) Long lines only
d)Any line

Ans: c

40.Recovery voltage is the value of RMS voltage that reappears across the poles of a circuit breaker before_______________ 
a. Restriking voltage
b. Final arc extinction
c. Rise of voltage
d. All of the above

Ans: b

41.The making and breaking currents of a 3 phase ac circuit breakers in power systems are respectively in ________form. 
a. rms value, rms value
b. Peak Value, rms value
c. rms value, instantaneous value
d. instantaneous value, instantaneous value 

Ans: b

42. What is restriking voltage? 
a. The transient voltage that appears across the circuit breaker contacts at the instant of arc extinction.
b. The transient voltage that appears across the circuit breaker contacts at the end of arc extinction.
c. Both (a) and (b)
d. None of the above 

Ans: a

43.Power station and sub-stations are protected against direct strokes of lightning using 
a) Rod gap arrester
b)Overhead ground wires
c) Earthing screen
d)Horn gap arrester 

Ans: c

44. In Busbar protection what is method of providing an earthed metal barrier surrounding a Busbar throughout its length called? 
a)Fault bus protection
b)Distance protection
c)Differential protection
d)Time graded over current protection

Ans: a

45.Solid-state power supplies are protected from high voltage surges
due to lightning using: 
a) Metal glaze resistors
b) Silicon-carbide varistor
c) Zinc-oxide-based varistor
d)Metal film resistors 

Ans: b

46. Arc in a circuit breaker is interrupted at 
a) Minimum voltage
b)Maximum current
c) Zero current
d)Maximum voltage

Ans: c

47.Keeping in view the cost and the overall effectiveness, which of the following circuit breaker is best suited for capacitor bank switching? 
a. Vacuum circuit breaker
b. Air blast CB
c. SF6
d. Oil CB 

Ans: a

48.The relay used for feeder protection 
a) Undervoltage relay
b) Translay relay
c) Thermal relay
d) Buchholz relay

Ans: b

49.A distance relay is said to be inherently directional if its characteristic
on R-X diagram: 
a) Is a straight line offset from origin
b)Is a circle that passes through origin
c) Is a circle that encloses origin
d)Is a straight line passes through origin 

Ans: b

50.The inverse definite mean time relays are used for over current and earth fault protection of transformer against 
(a) heavy loads
(b) internal short-circuits
(c) external short-circuits
(d) all of the above 

Ans: b

51. To limit current chopping in vacuum circuit breakers, the contact material employed should have the properties of (A)
a. Low conductivity and high vapour pressure.
b. Low conductivity and low vapour pressure.
c. High conductivity and high vapour pressure.
d. High conductivity and low vapour pressure.

Ans: a 

52.Match List-I ( Type of relays) with List-II ( Protective schemes) and select the correct
answer

List-I                                                                                                                                                     

A) Negative-sequence relay                          
B) Harmonic-restraint differential relay         
C) Over-current relay with time-delay           
D) Mho relay                                                  

LIST-II 

  1. Distribution feeder protection
  2. Long h.t line protection
  3. Transformer protection
  4. Rotor protection alternators   

Codes: 

   A B C D
a) 4 3 1 2
b) 1 2 4 3
c) 4 2 1 3
d) 1 3 4 2

Ans: a

53. The interrupting time of a circuit breaker is the period between the instant of _________. 
a. Initiation of short circuit and the arc extinction on an opening operation.
b. Energizing the trip circuit and the arc extension on an opening operation.
c. Initiation of short circuit and the parting of primary arc contacts.
d. Energizing of the trip circuit and the parting of primary arc contacts.

Ans: b